DP Flow Transmitter Calculator
Calculate flow, flow percentage and 4–20 mA output from differential pressure using the square-root relationship.
inH₂O
Current differential pressure measured by the transmitter
Select where the square-root calculation is performed
% Flow
Set to zero if no low-flow cutoff is required
DP Percentage
—
Flow Percentage
—
Calculated Flow
—
Transmitter Output
—
DCS Flow Indication
—
Linear DP Equivalent
—
DP and Flow Relationship
| DP Input | Flow | Square-Root Output | Linear DP Output |
|---|---|---|---|
| 0% | 0% | 4.00 mA | 4.00 mA |
| 1% | 10% | 5.60 mA | 4.16 mA |
| 4% | 20% | 7.20 mA | 4.64 mA |
| 9% | 30% | 8.80 mA | 5.44 mA |
| 25% | 50% | 12.00 mA | 8.00 mA |
| 49% | 70% | 15.20 mA | 11.84 mA |
| 81% | 90% | 18.40 mA | 16.96 mA |
| 100% | 100% | 20.00 mA | 20.00 mA |